{"dataType":"CVE_RECORD","dataVersion":"5.2","cveMetadata":{"cveId":"CVE-2026-1773","assignerOrgId":"e383dce4-0c27-4495-91c4-0db157728d17","state":"PUBLISHED","assignerShortName":"Hitachi Energy","dateReserved":"2026-02-02T16:28:59.394Z","datePublished":"2026-02-24T13:13:17.990Z","dateUpdated":"2026-02-28T02:20:00.192Z"},"containers":{"cna":{"affected":[{"defaultStatus":"unaffected","product":"RTU500 series CMU firmware","vendor":"Hitachi Energy","versions":[{"lessThanOrEqual":"12.7.7","status":"affected","version":"12.7.1","versionType":"custom"},{"lessThanOrEqual":"13.5.4","status":"affected","version":"13.5.1","versionType":"custom"},{"lessThanOrEqual":"13.6.2","status":"affected","version":"13.6.1","versionType":"custom"},{"lessThanOrEqual":"13.7.7","status":"affected","version":"13.7.1","versionType":"custom"},{"status":"affected","version":"13.8.1","versionType":"custom"}]}],"descriptions":[{"lang":"en","supportingMedia":[{"base64":false,"type":"text/html","value":"IEC 60870-5-104: Potential Denial of Service impact on reception of invalid U-format frame.&nbsp;Product is only affected if IEC 60870-5-104 bi-directional functionality is configured. Enabling secure communication following IEC 62351-3 does not remediate the vulnerability but mitigates the risk of exploitation.<br>"}],"value":"IEC 60870-5-104: Potential Denial of Service impact on reception of invalid U-format frame. Product is only affected if IEC 60870-5-104 bi-directional functionality is configured. Enabling secure communication following IEC 62351-3 does not remediate the vulnerability but mitigates the risk of exploitation."}],"impacts":[{"capecId":"CAPEC-278","descriptions":[{"lang":"en","value":"CAPEC-278 Web Services Protocol Manipulation"}]}],"metrics":[{"cvssV4_0":{"Automatable":"NOT_DEFINED","Recovery":"NOT_DEFINED","Safety":"NOT_DEFINED","attackComplexity":"LOW","attackRequirements":"NONE","attackVector":"NETWORK","baseScore":8.7,"baseSeverity":"HIGH","exploitMaturity":"NOT_DEFINED","privilegesRequired":"NONE","providerUrgency":"NOT_DEFINED","subAvailabilityImpact":"NONE","subConfidentialityImpact":"NONE","subIntegrityImpact":"NONE","userInteraction":"NONE","valueDensity":"NOT_DEFINED","vectorString":"CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N","version":"4.0","vulnAvailabilityImpact":"HIGH","vulnConfidentialityImpact":"NONE","vulnIntegrityImpact":"NONE","vulnerabilityResponseEffort":"NOT_DEFINED"},"format":"CVSS","scenarios":[{"lang":"en","value":"GENERAL"}]}],"problemTypes":[{"descriptions":[{"cweId":"CWE-184","description":"CWE-184 Incomplete List of Disallowed Inputs","lang":"en","type":"CWE"}]}],"providerMetadata":{"orgId":"e383dce4-0c27-4495-91c4-0db157728d17","shortName":"Hitachi Energy","dateUpdated":"2026-02-24T13:40:55.104Z"},"references":[{"url":"https://publisher.hitachienergy.com/preview?DocumentID=8DBD000237&LanguageCode=en&DocumentPartId=&Action=Launch"}],"source":{"discovery":"UNKNOWN"},"x_generator":{"engine":"Vulnogram 0.5.0"}},"adp":[{"metrics":[{"other":{"type":"ssvc","content":{"timestamp":"2026-02-28T02:19:44.432868Z","id":"CVE-2026-1773","options":[{"Exploitation":"none"},{"Automatable":"yes"},{"Technical Impact":"partial"}],"role":"CISA Coordinator","version":"2.0.3"}}}],"title":"CISA ADP Vulnrichment","providerMetadata":{"orgId":"134c704f-9b21-4f2e-91b3-4a467353bcc0","shortName":"CISA-ADP","dateUpdated":"2026-02-28T02:20:00.192Z"}}]}}