{"dataType":"CVE_RECORD","dataVersion":"5.2","cveMetadata":{"cveId":"CVE-2026-127057","assignerOrgId":"d7ff35af-cf88-454c-bab9-af60602f10f8","state":"PUBLISHED","assignerShortName":"Danfoss","dateReserved":"2026-11-12T12:46:22.614Z","datePublished":"2026-11-20T10:52:24.467Z","dateUpdated":"2026-11-20T16:39:10.395Z"},"containers":{"cna":{"providerMetadata":{"orgId":"d7ff35af-cf88-454c-bab9-af60602f10f8","shortName":"Danfoss","dateUpdated":"2026-11-20T10:52:24.467Z"},"title":"Exploitation of Weak or Known Passwords in Danfoss AK-SC 355 and AK-SM 800 Series","problemTypes":[{"descriptions":[{"lang":"en","cweId":"CWE-1392","description":"CWE-1392 Use of default credentials","type":"CWE"}]}],"affected":[{"vendor":"Danfoss","product":"AK-SC 355","versions":[{"status":"affected","version":"0","lessThanOrEqual":"latest","versionType":"custom"}],"defaultStatus":"affected"},{"vendor":"Danfoss","product":"AK-SM 800","versions":[{"status":"affected","version":"0","lessThanOrEqual":"latest","versionType":"custom"}],"defaultStatus":"affected"}],"descriptions":[{"lang":"en","value":"The\nDanfoss legacy AK-SC 355 and AK-SM 800 Series are vulnerable to unauthorized\naccess when default credentials or known passwords are used for authentication.\nThese products were manufactured with default credentials documented in the\nproduct manual. All versions are affected.","supportingMedia":[{"type":"text/html","base64":false,"value":"<p>The\nDanfoss legacy AK-SC 355 and AK-SM 800 Series are vulnerable to unauthorized\naccess when default credentials or known passwords are used for authentication.\nThese products were manufactured with default credentials documented in the\nproduct manual. All versions are affected.<strong> </strong></p>"}]}],"references":[{"url":"https://www.danfoss.com/en/service-and-support/coordinated-vulnerability-disclosure/danfoss-security-advisories/dsa-2026-12-02/"}],"metrics":[{"format":"CVSS","scenarios":[{"lang":"en","value":"GENERAL"}],"cvssV4_0":{"attackVector":"NETWORK","attackComplexity":"LOW","attackRequirements":"NONE","privilegesRequired":"NONE","userInteraction":"NONE","vulnConfidentialityImpact":"HIGH","subConfidentialityImpact":"LOW","vulnIntegrityImpact":"HIGH","subIntegrityImpact":"LOW","vulnAvailabilityImpact":"HIGH","subAvailabilityImpact":"HIGH","exploitMaturity":"NOT_DEFINED","Safety":"NOT_DEFINED","Automatable":"NOT_DEFINED","Recovery":"NOT_DEFINED","valueDensity":"NOT_DEFINED","vulnerabilityResponseEffort":"NOT_DEFINED","providerUrgency":"NOT_DEFINED","version":"4.0","baseSeverity":"CRITICAL","baseScore":9.9,"vectorString":"CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:L/SI:L/SA:H"}}],"workarounds":[{"lang":"en","value":"*  \n\nRemove\ninternet exposure of affected units and of all units exposed on public IP\n\n\n  *  \n\nRecommend\nusing strong and unique passwords\n\n\n  *  \n\nRe-establish\naccess to the units only through a secure VPN or in general over a protected\nnetwork","supportingMedia":[{"type":"text/html","base64":false,"value":"<p></p><ul><li><p>Remove\ninternet exposure of affected units and of all units exposed on public IP</p></li><li><p><span>Recommend\nusing strong and unique passwords</span></p></li><li><p><span>Re-establish\naccess to the units only through a secure VPN or in general over a protected\nnetwork</span></p></li></ul><p></p>"}]}],"solutions":[{"lang":"en","value":"*  \n\nInstall according to the instructions of the manual, avoiding public IP exposure\n\n\n  *  \n\nUpdate the fleet (AK-SC355, AK-SM800) to current generation products (AK-SM800A series), to ensure receiving continuous cybersecurity updates.","supportingMedia":[{"type":"text/html","base64":false,"value":"<ul><li><p>Install according to the instructions of the manual, avoiding public IP exposure</p></li><li><p>Update the fleet (AK-SC355, AK-SM800) to current generation products (AK-SM800A series), to ensure receiving continuous cybersecurity updates.</p></li></ul>"}]}],"source":{"discovery":"UNKNOWN"},"x_generator":{"engine":"Vulnogram 1.0.5"}},"adp":[{"metrics":[{"other":{"type":"ssvc","content":{"timestamp":"2026-11-20T16:23:24.639923Z","id":"CVE-2026-127057","options":[{"Exploitation":"none"},{"Automatable":"yes"},{"Technical Impact":"total"}],"role":"CISA Coordinator","version":"2.0.3"}}}],"title":"CISA ADP Vulnrichment","providerMetadata":{"orgId":"134c704f-9b21-4f2e-91b3-4a467353bcc0","shortName":"CISA-ADP","dateUpdated":"2026-11-20T16:39:10.395Z"}}]}}