{"dataType":"CVE_RECORD","dataVersion":"5.1","cveMetadata":{"cveId":"CVE-2023-1285","assignerOrgId":"e0f77b61-78fd-4786-b3fb-1ee347a748ad","state":"PUBLISHED","assignerShortName":"Mitsubishi","dateReserved":"2023-03-09T08:05:46.845Z","datePublished":"2023-04-14T02:17:55.175Z","dateUpdated":"2025-02-06T20:57:38.924Z"},"containers":{"cna":{"affected":[{"defaultStatus":"unaffected","product":"GC-ENET-COM","vendor":"Mitsubishi Electric India","versions":[{"status":"affected","version":"SN:16XXXXXXXXX"}]}],"descriptions":[{"lang":"en","supportingMedia":[{"base64":false,"type":"text/html","value":"Signal Handler Race Condition vulnerability in Mitsubishi Electric India GC-ENET-COM whose first 2 digits of 11-digit serial number of unit are \"16\" allows a remote unauthenticated attacker to cause a denial-of-service (DoS) condition in Ethernet communication by sending a large number of specially crafted packets to any UDP port when GC-ENET-COM is configured as a Modbus TCP Server. The communication resumes only when the power of the main unit is turned off and on or when the GC-ENET-COM is hot-swapped from the main unit.<br>"}],"value":"Signal Handler Race Condition vulnerability in Mitsubishi Electric India GC-ENET-COM whose first 2 digits of 11-digit serial number of unit are \"16\" allows a remote unauthenticated attacker to cause a denial-of-service (DoS) condition in Ethernet communication by sending a large number of specially crafted packets to any UDP port when GC-ENET-COM is configured as a Modbus TCP Server. The communication resumes only when the power of the main unit is turned off and on or when the GC-ENET-COM is hot-swapped from the main unit.\n"}],"metrics":[{"cvssV3_1":{"attackComplexity":"LOW","attackVector":"NETWORK","availabilityImpact":"HIGH","baseScore":7.5,"baseSeverity":"HIGH","confidentialityImpact":"NONE","integrityImpact":"NONE","privilegesRequired":"NONE","scope":"UNCHANGED","userInteraction":"NONE","vectorString":"CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H","version":"3.1"},"format":"CVSS","scenarios":[{"lang":"en","value":"GENERAL"}]}],"problemTypes":[{"descriptions":[{"cweId":"CWE-364","description":"CWE-364 Signal Handler Race Condition","lang":"en","type":"CWE"}]}],"providerMetadata":{"orgId":"e0f77b61-78fd-4786-b3fb-1ee347a748ad","shortName":"Mitsubishi","dateUpdated":"2023-04-14T02:17:55.175Z"},"references":[{"tags":["vendor-advisory"],"url":"https://mitsubishielectric.in/fa/cnc-pdf/DoS_in_Ethernet_Communication_Extension_Unit_GC_ENET_COM_of_GOC35_Series.pdf"},{"tags":["government-resource"],"url":"https://www.cisa.gov/news-events/ics-advisories/icsa-23-103-15"}],"source":{"discovery":"UNKNOWN"},"x_generator":{"engine":"Vulnogram 0.1.0-dev"}},"adp":[{"providerMetadata":{"orgId":"af854a3a-2127-422b-91ae-364da2661108","shortName":"CVE","dateUpdated":"2024-08-02T05:41:00.062Z"},"title":"CVE Program Container","references":[{"tags":["vendor-advisory","x_transferred"],"url":"https://mitsubishielectric.in/fa/cnc-pdf/DoS_in_Ethernet_Communication_Extension_Unit_GC_ENET_COM_of_GOC35_Series.pdf"},{"tags":["government-resource","x_transferred"],"url":"https://www.cisa.gov/news-events/ics-advisories/icsa-23-103-15"}]},{"metrics":[{"other":{"type":"ssvc","content":{"timestamp":"2025-02-06T20:56:57.330519Z","id":"CVE-2023-1285","options":[{"Exploitation":"none"},{"Automatable":"yes"},{"Technical Impact":"partial"}],"role":"CISA Coordinator","version":"2.0.3"}}}],"title":"CISA ADP Vulnrichment","providerMetadata":{"orgId":"134c704f-9b21-4f2e-91b3-4a467353bcc0","shortName":"CISA-ADP","dateUpdated":"2025-02-06T20:57:38.924Z"}}]}}