{"containers":{"cna":{"affected":[{"product":"Intelligent Power manager (IPM)","vendor":"Eaton","versions":[{"lessThan":"1.69","status":"affected","version":"unspecified","versionType":"custom"}]}],"credits":[{"lang":"en","value":"Amir Preminger from Claroty research"}],"datePublic":"2021-04-01T00:00:00.000Z","descriptions":[{"lang":"en","value":"Eaton Intelligent Power Manager (IPM) prior to 1.69 is vulnerable to authenticated SQL injection. A malicious user can send a specially crafted packet to exploit the vulnerability. Successful exploitation of this vulnerability can allow attackers to add users in the data base."}],"metrics":[{"cvssV3_1":{"attackComplexity":"HIGH","attackVector":"ADJACENT_NETWORK","availabilityImpact":"HIGH","baseScore":7.1,"baseSeverity":"HIGH","confidentialityImpact":"HIGH","integrityImpact":"HIGH","privilegesRequired":"LOW","scope":"UNCHANGED","userInteraction":"NONE","vectorString":"CVSS:3.1/AV:A/AC:H/PR:L/UI:N/S:U/C:H/I:H/A:H","version":"3.1"}}],"problemTypes":[{"descriptions":[{"cweId":"CWE-89","description":"CWE-89 SQL Injection","lang":"en","type":"CWE"}]}],"providerMetadata":{"dateUpdated":"2021-04-13T18:03:08.000Z","orgId":"63703b7d-23e2-41ef-94b3-a3c6333f7759","shortName":"Eaton"},"references":[{"tags":["x_refsource_MISC"],"url":"https://www.eaton.com/content/dam/eaton/company/news-insights/cybersecurity/security-bulletins/eaton-intelligent-power-manager-ipm-vulnerability-advisory.pdf"}],"solutions":[{"lang":"en","value":"upgrade the software to latest version 1.69"}],"source":{"advisory":"ETN-VA-2021-1000","defect":["ETN-VA-2021-1000"],"discovery":"EXTERNAL"},"title":"Improper Neutralization of Special Elements used in an SQL Command","workarounds":[{"lang":"en","value":"To prevent the exploitation of the issues and safeguard the software from malicious entities, Eaton recommends blocking ports 4679 & 4680 at the enterprise network or home network where Intelligent Power Manager (IPM) software is installed and used"}],"x_generator":{"engine":"Vulnogram 0.0.9"},"x_legacyV4Record":{"CVE_data_meta":{"AKA":"SQL Injection","ASSIGNER":"CybersecurityCOE@eaton.com","DATE_PUBLIC":"2021-04-01T07:00:00.000Z","ID":"CVE-2021-23276","STATE":"PUBLIC","TITLE":"Improper Neutralization of Special Elements used in an SQL Command"},"affects":{"vendor":{"vendor_data":[{"product":{"product_data":[{"product_name":"Intelligent Power manager (IPM)","version":{"version_data":[{"version_affected":"<","version_value":"1.69"}]}}]},"vendor_name":"Eaton"}]}},"credit":[{"lang":"eng","value":"Amir Preminger from Claroty research"}],"data_format":"MITRE","data_type":"CVE","data_version":"4.0","description":{"description_data":[{"lang":"eng","value":"Eaton Intelligent Power Manager (IPM) prior to 1.69 is vulnerable to authenticated SQL injection. A malicious user can send a specially crafted packet to exploit the vulnerability. Successful exploitation of this vulnerability can allow attackers to add users in the data base."}]},"generator":{"engine":"Vulnogram 0.0.9"},"impact":{"cvss":{"attackComplexity":"HIGH","attackVector":"ADJACENT_NETWORK","availabilityImpact":"HIGH","baseScore":7.1,"baseSeverity":"HIGH","confidentialityImpact":"HIGH","integrityImpact":"HIGH","privilegesRequired":"LOW","scope":"UNCHANGED","userInteraction":"NONE","vectorString":"CVSS:3.1/AV:A/AC:H/PR:L/UI:N/S:U/C:H/I:H/A:H","version":"3.1"}},"problemtype":{"problemtype_data":[{"description":[{"lang":"eng","value":"CWE-89 SQL Injection"}]}]},"references":{"reference_data":[{"name":"https://www.eaton.com/content/dam/eaton/company/news-insights/cybersecurity/security-bulletins/eaton-intelligent-power-manager-ipm-vulnerability-advisory.pdf","refsource":"MISC","url":"https://www.eaton.com/content/dam/eaton/company/news-insights/cybersecurity/security-bulletins/eaton-intelligent-power-manager-ipm-vulnerability-advisory.pdf"}]},"solution":[{"lang":"en","value":"upgrade the software to latest version 1.69"}],"source":{"advisory":"ETN-VA-2021-1000","defect":["ETN-VA-2021-1000"],"discovery":"EXTERNAL"},"work_around":[{"lang":"en","value":"To prevent the exploitation of the issues and safeguard the software from malicious entities, Eaton recommends blocking ports 4679 & 4680 at the enterprise network or home network where Intelligent Power Manager (IPM) software is installed and used"}]}},"adp":[{"providerMetadata":{"orgId":"af854a3a-2127-422b-91ae-364da2661108","shortName":"CVE","dateUpdated":"2024-08-03T19:05:54.415Z"},"title":"CVE Program Container","references":[{"tags":["x_refsource_MISC","x_transferred"],"url":"https://www.eaton.com/content/dam/eaton/company/news-insights/cybersecurity/security-bulletins/eaton-intelligent-power-manager-ipm-vulnerability-advisory.pdf"}]}]},"cveMetadata":{"assignerOrgId":"63703b7d-23e2-41ef-94b3-a3c6333f7759","assignerShortName":"Eaton","cveId":"CVE-2021-23276","datePublished":"2021-04-13T18:03:08.524Z","dateReserved":"2021-01-08T00:00:00.000Z","dateUpdated":"2024-09-17T02:22:03.243Z","state":"PUBLISHED"},"dataType":"CVE_RECORD","dataVersion":"5.1"}