{"containers":{"cna":{"affected":[{"product":"SIPROTEC 4 and SIPROTEC Compact relays equipped with EN100 Ethernet communication modules","vendor":"Siemens AG","versions":[{"status":"affected","version":"All versions"}]}],"descriptions":[{"lang":"en","value":"A vulnerability has been identified in SIPROTEC 4 and SIPROTEC Compact relays equipped with EN100 Ethernet communication modules (All versions). Specially crafted packets sent to port 50000/UDP of the EN100 Ethernet communication modules could cause a Denial-of-Service of the affected device. A manual reboot is required to recover the service of the device. At the time of advisory publication no public exploitation of this security vulnerability was known to Siemens."}],"problemTypes":[{"descriptions":[{"cweId":"CWE-20","description":"CWE-20: Improper Input Validation","lang":"en","type":"CWE"}]}],"providerMetadata":{"dateUpdated":"2020-03-10T19:16:17.000Z","orgId":"cec7a2ec-15b4-4faf-bd53-b40f371f3a77","shortName":"siemens"},"references":[{"tags":["x_refsource_MISC"],"url":"https://cert-portal.siemens.com/productcert/pdf/ssa-974843.pdf"}],"x_legacyV4Record":{"CVE_data_meta":{"ASSIGNER":"productcert@siemens.com","ID":"CVE-2019-19279","STATE":"PUBLIC"},"affects":{"vendor":{"vendor_data":[{"product":{"product_data":[{"product_name":"SIPROTEC 4 and SIPROTEC Compact relays equipped with EN100 Ethernet communication modules","version":{"version_data":[{"version_value":"All versions"}]}}]},"vendor_name":"Siemens AG"}]}},"data_format":"MITRE","data_type":"CVE","data_version":"4.0","description":{"description_data":[{"lang":"eng","value":"A vulnerability has been identified in SIPROTEC 4 and SIPROTEC Compact relays equipped with EN100 Ethernet communication modules (All versions). Specially crafted packets sent to port 50000/UDP of the EN100 Ethernet communication modules could cause a Denial-of-Service of the affected device. A manual reboot is required to recover the service of the device. At the time of advisory publication no public exploitation of this security vulnerability was known to Siemens."}]},"problemtype":{"problemtype_data":[{"description":[{"lang":"eng","value":"CWE-20: Improper Input Validation"}]}]},"references":{"reference_data":[{"name":"https://cert-portal.siemens.com/productcert/pdf/ssa-974843.pdf","refsource":"MISC","url":"https://cert-portal.siemens.com/productcert/pdf/ssa-974843.pdf"}]}}},"adp":[{"providerMetadata":{"orgId":"af854a3a-2127-422b-91ae-364da2661108","shortName":"CVE","dateUpdated":"2024-08-05T02:09:39.609Z"},"title":"CVE Program Container","references":[{"tags":["x_refsource_MISC","x_transferred"],"url":"https://cert-portal.siemens.com/productcert/pdf/ssa-974843.pdf"}]}]},"cveMetadata":{"assignerOrgId":"cec7a2ec-15b4-4faf-bd53-b40f371f3a77","assignerShortName":"siemens","cveId":"CVE-2019-19279","datePublished":"2020-03-10T19:16:17.000Z","dateReserved":"2019-11-26T00:00:00.000Z","dateUpdated":"2024-08-05T02:09:39.609Z","state":"PUBLISHED"},"dataType":"CVE_RECORD","dataVersion":"5.1"}